Service Error Codes
-
To Reset Service Errors:
- Put the boiler into standby mode (the power icon lights up red).
- Turn off the boiler’s circuit breaker in the electrical panel for at least 1 minute.
- After 1 minute, reconnect the boiler to the power supply and turn it on.
- If the error persists, use the error instructions provided below.
-
Error E1: Detected Current Leak
Possible Causes:
- Insulation failure of the cable.
- Moisture accumulation on the live parts of the boiler.
- Breakdown of one or more heating elements in the block to the protective casing.
Troubleshooting:
- Turn off the boiler by switching off the circuit breaker in the electrical panel.
- Contact an authorized service center.
Warning: When error E1 is displayed, there is a high risk of electric shock. The use of the boiler is strictly prohibited until the causes of the error are eliminated.
-
Error E2: Circulant Flow Violation
Possible Causes:
- One of the valves under the boiler is closed, or the automatic thermostatic valve (thermostatic head) has closed.
- The coarse filter located at the boiler inlet is clogged.
- Presence of air in the heating system.
- Faulty automatic air vent.
- Voltage in the electrical system is below permissible (the circulation pump has stopped).
- Voltage in the electrical system is above permissible (the fuse has blown).
- Absence of one phase in a three-phase boiler connection.
- Water flow through the boiler is less than 3.7 liters per minute.
- Leakage of the heating medium from the heating system (low level).
- Contamination or malfunction of the flow sensor.
- Faulty three-way valve (with DHW system connected).
- Faulty circulation pump.
Troubleshooting:
- Ensure all heating system valves and DHW circuit valves are open.
- Ensure the three-way DHW circuit valve switches freely.
- Ensure the coarse filter is not clogged.
- Visually inspect the heating system and DHW circuit for leaks. If necessary, fill the system to the recommended pressure of 1.2–1.5 bar. Monitor the pressure using the boiler gauge.
- Check the flow of the heating medium through the boiler using service menu parameters P1, P2, and P3.
- Remove air from the heating system and DHW circuit.
- Check the voltage in the network (it should comply with the standards in your region).
- Check the condition of air vents in the heating system and, if necessary, remove air from the heating system and DHW circuit.
- Contact an authorized service center.
-
Error E3: Outlet Temperature Sensor Error
Possible Causes:
- Lack of connection between the sensor and the boiler control unit.
- Faulty sensor.
Troubleshooting:
- Contact an authorized service center.
Warning: Using the boiler is prohibited until error E3 is eliminated.
-
Error E4: Room Temperature Sensor Error
Possible Causes:
- Lack of connection between the sensor and the boiler control unit.
- Faulty sensor.
Troubleshooting:
- Contact an authorized service center.
Note: The boiler is allowed to operate with error E4.
-
Error E5: Indirect Heating Boiler Water Temperature Sensor Error
Possible Causes:
- Lack of connection between the sensor and the boiler control unit.
- Faulty sensor.
Troubleshooting:
- Contact an authorized service center.
Warning:
- The boiler operation in DHW mode is prohibited.
- Boiler operation is allowed only in heating mode.
-
Error E6: Overheating (Heating Medium Temperature Exceeds 90°C)
Possible Causes:
- Faulty control unit.
- Faulty heating medium temperature sensor.
Troubleshooting:
- Turn off the boiler until the temperature drops to 65°C or below, then restart it.
- If the error persists, contact an authorized service center.
Note: Error E6 disappears automatically when the heating medium cools to 65°C. When error E6 occurs, heating stops.
-
Error E7: Frost Protection System Activated
Possible Cause:
- The temperature in the heating medium dropped below +5°C. Consequently, the frost protection system automatically activates, and the AFr mode is displayed. The application sends a message in the form of error E7.
Troubleshooting:
- The boiler automatically switches to heating mode and heats the system to +30°C, after which it automatically returns to standby mode.
Note: Information about error E7 in the attached video differs due to the boiler program update.
-
Error E0: General System Failure
Possible Cause:
- Boiler control system failure.
Troubleshooting:
- Reset parameter P10 to factory settings in the service menu.
-
Error ER1: Boiler Not Working
Possible Causes:
- The boiler’s power was turned off by the circuit breaker in the panel with a violation of instructions. The boiler was disconnected from the power supply without first being put into standby mode.
- General power system failure. The boiler’s power was turned off with a violation of instructions.
- Unreliable connection of the touch display cable to the boiler control board.
- Global software failure.
Troubleshooting:
- Remove the boiler cover and check the connection of the touch display cable to the boiler control board.
- If the error does not disappear, contact an authorized service center.
-
No Button Indication (Boiler Not Working)
Possible Cause:
- The boiler overheated, and the high-temperature safety thermostat was triggered.
Troubleshooting:
- Cool the boiler to a temperature of at least 65°C.
- Remove the boiler cover and press the button on the high-temperature safety thermostat.
- If the error does not disappear, contact an authorized service center.